explosion proof air conditioners

MATTICKS INDUSTRIES, INC.

explosion proof air conditioners

tticks I

Matticks Industries, Inc.

CONVECTION HEATERS

FOR

HAZARDOUS LOACATIONS

CLASS 1, GROUP B-C-D, DIVISION 1 & 2


Ratings:

From 0.5kw to 9.5kw

FM & CSA Approved for Class I, Group BCD, Division 1&2 and Group EFG, Division 1&2

Built-in overtemperature thermal cutout for additional safety.

Heating Elements are Industrial Grade with high grade resistance wiring

( 80% Nickel / 20% Chromium )

Units available for Gas and Dust Atmospheres.

Wet locations are covered to with available iridite-coated elements and powder coated frames.

Sloped Top Cabinet:

This is the preferred construction for hazardous areas. The slope top can prevent objects from being set on top of the heater, which could restrict airflow.

Optional:

Thermostat included for wall mounting. (C&D Rated or BCD Rated)

Built in controls - contactor, transdformer, or thermostat

Both single and three phase voltages are available

 

Single Phase Units: Class I, Group BCD, Division 1&2........ Rated T2A

 MODEL  KW  VOLTS
 PHASE
 AMPS  UNIT SIZE  IGNITON TEMP.
 254-F0310052B 0.5 120  1 4.2 1  536 degF T2A
254-F0310052C 0.5 208  1 2.4 1  536 degF T2A
254-F0310052J 0.5 240  1 2.1 1  536 degF T2A
254-F0310102B 1.0 120  1 8.3 1  536 degF T2A
254-F0310102C 1.0 208  1 4.8 1  536 degF T3A
254-F0310102J 1.0 240  1 4.2 1  536 degF T2A
254-F0320182B 1.8 120  1 15.0 2  536 degF T2A
254-F0320182C 1.8 208  1 8.7 2  536 degF T2A
254-F0320182J 1.8 240  1 7.5 2  536 degF T2A
254-F0320252C 2.5 208  1 12.0 2  536 degF T2A
254-F0320252J 2.5 240  1 10.2 2  536 degF T2A
254-F0330362C 3.6 208  1 17.3 3  536 degF T2A
254-F0330362J 3.6 240  1 15.0 3  536 degF T2A
254-F0330442J 4.4 240  1 18.3 3  536 degF T2A
254-F0340652J 6.5 240  1 27.1 4  536 degF T2A
254-F0340752J 7.5 240  1 31.3 4  536 degF T2A
254-F0340952J 9.5 240  1 39.6 4  536 degF T2A
             

254-F0340652J / 254-F0340752J / 254-F0340952J --- Magnetic contactor required

Three Phase Units: Class I, Group BCD, Division 1&2........ Rated T2A

 MODEL  KW  VOLTS
 PHASE
 AMPS  UNIT SIZE  IGNITON TEMP.
254-F0320182U 1.8 480 3 1.3 2  536 degF T2A
254-F0320252D 2.5 208 3 6.9 2  536 degF T2A
254-F0320252U 2.5 480 3 3.0 2  536 degF T2A
254-F0330362D 3.6 208 3 10.0 3  536 degF T2A
254-F0330362U 3.6 480 3 4.3 3  536 degF T2A
254-F0330442D 4.4 280 3 12.2 3  536 degF T2A
254-F0330442U 4.4 480 3 5.3 3  536 degF T2A
254-F0340652D 6.5 208 3 18.0 4  536 degF T2A
254-F0340652U 6.5 480 3 7.8 4  536 degF T2A
254-F0340752D 7.5 208 3 20.8 4  536 degF T2A
254-F0340752U 7.5 480 3 9.0 4  536 degF T2A
254-F0340952D 9.5 208 3 26.4 4  536 degF T2A
254-F00340952U 9.5 480 3 11.4 4  536 degF T2A
             

208 VOLT UNITS --- Magnetic contactor required

480 VOLT UNITS --- Magnetic contactor and control transformer required

 

Single Phase Units: Class I, Group BCD, Division 1&2........ Rated T3A

 MODEL  KW  VOLTS
 PHASE
 AMPS  UNIT SIZE  IGNITON TEMP.
254-F0610052B 0.5 120  1 4.2 1  356 degF T3A
254-F0610052C 0.5 208  1 2.4 1 356 degF T3A
254-F0610052J 0.5 240  1 2.1 1 356 degF T3A
254-F0620142B 1.4 120  1 11.7 2 356 degF T3A
254-F0620142C 1.4 208  1 6.7 2  356 degF T3A
254-F0620142J 1.4 240  1 5.8 2  356 degF T3A
254-F0630232B 2.3 120  1 19.2 3  356 degF T3A
254-F0630232C 2.3 208  1 11.1 3  356 degF T3A
254-F0630232J 2.3 240  1 9.6 3  356 degF T3A
254-F0640322C 3.2 208  1 15.4 4  356 degF T3A
254-F0640322J 3.2 240  1 13.3 4  356 degF T3A
254-F0640502J 5.0 240  1 20.8 4  356 degF T3A
             

 

Three Phase Units: Class I, Group BCD, Division 1&2........ Rated T3A

 MODEL  KW  VOLTS
 PHASE
 AMPS  UNIT SIZE  IGNITON TEMP.
254-F0630232D 2.3 208 3 6.4 3  356 degF T3A
254-F0630232U 2.3 480 3 2.8 3  356 degF T3A
254-F0640332D 3.2 208 3 8.9 4  356 degF T3A
254-F0640322U 3.2 480 3 3.8 4  356 degF T3A
254-F0640502D 5.0 208 3 13.9 4  356 degF T3A
254-F0640502U 5.0 480 3 6.0 4  356 degF T3A
             

208 VOLT UNITS --- Magnetic contactor required

480 VOLT UNITS --- Magnetic contactor and control transformer required

Single Phase Units: Class II, Group EFG, Division 1&2........ Rated T3C

 MODEL  KW  VOLTS
 PHASE
 AMPS  UNIT SIZE  IGNITON TEMP.
254-F0810054B 0.5 120  1 4.2 1  320 degF T3C
254-F0810054C 0.5 208  1 2.4 1 320 degF T3C
254-F0810054J 0.5 240  1 2.1 1 320 degF T3C
254-F0820104B 1.0 120  1 8.3 2 320 degF T3C
254-F0820104C 1.0 208  1 4.8 2  320 degF T3C
254-F0820104J 1.0 240  1 4.2 2  320 degF T3C
254-F0830174B 1.7 120  1 14.2 3  320 degF T3C
254-F0830174C 1.7 208  1 8.2 3  320 degF T3C
254-F0830174J 1.7 240  1 7.1 3  320 degF T3C
254-F0840324C 3.2 208  1 15.4 4  320 degF T3C
254-F0840324J 3.2 240  1 13.3 4  320 degF T3C
             

 

Three Phase Units: Class I, Group BCD, Division 1&2........ Rated T3A

 MODEL  KW  VOLTS
 PHASE
 AMPS  UNIT SIZE  IGNITON TEMP.
254-F0830174U 1.7 480 3 2.0 3  320 degF T3C
254-F0840324D 3.2 208 3 8.9 4  320 degF T3C
254-F0840324U 3.2 480 3 3.8 4  320 degF T3C
             

208 VOLT UNITS --- Magnetic contactor required

480 VOLT UNITS --- Magnetic contactor and control transformer required

 UNIT SIZE  LENGTH
(cm)
 WIDTH
(cm)
 HEIGHT
(cm)
 WEIGHT - Lb (Kg)
 NET
1  26"
(66)
 8"
(20)
 6"
(15)
 13 Lbs
(5.9)
 2  26"
(66)
 8"
(20)
 16"
(40)
 27 Lbs
(12.2)
 3  39"
(99)
 8"
(20)
 16"
(40)
 36 Lbs
(16.3)
 4  67.5"
(171)
 8"
(20)
 16"
(40)
 60 Lbs
(27.2)
         


 

HOME PAGE