explosion proof air conditioners

MATTICKS INDUSTRIES, INC.

explosion proof air conditioners

tticks I

KOOLGUARDTM

WALL MOUNT COMBO

AIR CONDITIONING & PRESSURIZING

FOR HAZARDOUS LOCATIONS

"COOLING ONLY"

CLASS 1, GROUP BCD, DIVISION 2 EXTERIOR

GENERAL PURPOSE INTERIOR

NFPA 496 FOR Y, OR Z PRESSURIZING


Self Contained Controls

Cooling Only

230 Volt 1Ph , 230 Volt 3Ph, 460 Volt 3Ph @ 60Hz

Features:

Heavy duty ultra-quite operation for versatile applications such as new construction, modular analyzer shelters, control rooms, electronic equipment shelters, battery rooms, chemical storage containers, and many other hazardous locations that require environmental control.

Aluminum finned copper coils: Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.

Twin indoor blowers for the a/c side: Move air quietly. Single speed blower motor provides maximum room circulation and low static operation.

Compressors: Reciprocating compression designed to withstand higher compressor ratios. Scroll compressors for increased efficiency, quieter operation and reliability on 4 and 5 ton models.

Dust Filters: One inch disposable air filters are standard with the return air filter grill and are replaceable from the room side.

Easy Installation

One Cutout for mounting

Fresh Air Stack 25' from grade level

Options:...

Polyurethane enamel or Herisite corrosion protected hermetic system, includes evaporator coil, condenser coil, compressor, and all connecting tube

Loss of flow Alarm Contacts

Low Ambient Control

Stainless Steel Housing

Cooling Only Models :

18,000 BTU to 56,000 BTU @ 230/208 Volt 1Ph 60Hz

24,000 BTU to 70,000 BTU @ 230/208 Volt 3Ph 60Hz

31,000 BTU to 67,000 BTU @ 460 Volt 3Ph 60Hz

Pressurizer Section:

The Combo Units are offered with 2000 to 5000 CFM pressurizers

Single or Dual pressurizers

All Pressurizers are PLC Operated with Variable Speed Control

 

SPECIFICATIONS - 230/208 Volt 1Ph UNITS

 MODEL  COOLING CAPACITY
BTU/HR
 A/C UNIT ELECTRICAL RATINGS  A/C UNIT AIR MOVING CAPACITY  PRESSURIZER  RATINGS  PRESSURIZER  CFM
 VOLTS AMPS WATTS CIRCUIT RATING  VOLTS AMPS CIRCUIT RATING
 MBC218A-GP-BCD-P  18,300  230/208  9.2/10.2  2120/2120  20A  905 CFM  230/208  2.3/2.4  10A  2000
 MBC224A-GP-BCD-P  24,000  230/208  11.7/12.2  3500/3270  25A  905 CFM  230/208  2.3/2.4  10A  2000
 MBC231A-GP-BCD-P  31,000  230/208  16.3/17.4  4730/4390  35A  1270 CFM  230/208  2.3/2.4  10A  3000
 MBC236A-GP-BCD-P  36,000  230/208  19.4/20.7  5410/5180  40A  1270 CFM  230/208  2.3/2.4  10A  3000
 MBC243A-GP-BCD-P  43,000  230/208  23.3/25.5  6920/6620  50A  1665 CFM  230/208  2.3/2.4  10A  3000
 MBC247A-GP-BCD-P  47,500  230/208  26.4/28.5  7360/7080  50A  1665 CFM  230/208  2.3/2.4  10A  3000
 MBC257A-GP-BCD-P  57,500  230/208  31.8/34.4  9500/8700  70A  1665 CFM  230/208  2.3/2.4  10A  3000
                     

SPECIFICATIONS - 230/208 Volt 3Ph UNITS

 MODEL  COOLING CAPACITY
BTU/HR
 A/C UNIT ELECTRICAL RATINGS  A/C UNIT AIR MOVING CAPACITY  PRESSURIZER  RATINGS  PRESSURIZER  CFM
 VOLTS AMPS WATTS CIRCUIT RATING  VOLTS AMPS CIRCUIT RATING
 MBC224B-GP-BCD-P  24,000  230/208  8.8/9.1  3500/3270  15A  905 CFM  230/208  2.3/2.4  10A  2000
 MBC231B-GP-BCD-P  31,000  230/208  11.9/12.2  4730/4390  20A  1270 CFM  230/208  2.3/2.4  10A  3000
 MBC236A-GP-BCD-P  36,000  230/208  13.6/14.4  5410/5180  25A  1270 CFM  230/208  2.3/2.4  10A  3000
 MBC243B-GP-BCD-P  43,000  230/208  17.4/18.4  6920/6620  35A  1665 CFM  230/208  2.3/2.4  10A  3000
 MBC247B-GP-BCD-P  47,500  230/208  18.5/19.7  7360/7080  35A  1665 CFM  230/208  2.3/2.4  10A  3000
 MBC257B-GP-BCD-P  57,500  230/208  23.9/24.2  9500/8700  45A  1665 CFM  230/208  2.3/2.4  10A  3000
 MBC269B-GP-BCD-P  69,500  230/208  25.7/26.1  9500/8700  50A  1665 CFM  230/208  2.3/2.4  10A  3000
                     

SPECIFICATIONS - 460 Volt 3Ph UNITS

 MODEL  COOLING CAPACITY
BTU/HR
 A/C UNIT ELECTRICAL RATINGS  A/C UNIT AIR MOVING CAPACITY  PRESSURIZER  RATINGS  PRESSURIZER  CFM
 VOLTS AMPS WATTS CIRCUIT RATING  VOLTS AMPS CIRCUIT RATING
 MBC231C-GP-BCD-P  31,000  460  7.3  5800  10A  1270 CFM  460  1.2  5.0A  3000
 MBC236C-GP-BCD-P  36,000  460  7.7  6120  15A  1270 CFM  460  1.2  5.0A  3000
 MBC243C-GP-BCD-P  43,000  460  9.1  7240  15A  1665 CFM  460  1.2  5.0A  3000
 MBC247C-GP-BCD-P  47,500  460  9.9  7870  15A  1665 CFM  460  1.2  5.0A  3000
 MBC257C-GP-BCD-P  57,500  460  10.1  8030  15A  1900 CFM  460  1.2  5.0A  3000
 MBC267C-GP-BCD-P  67,000  460  14.8  11770  25A  1900 CFM  460  1.2  5.0A  3000
                     

DEMINSIONAL SPECIFICATIONS

 MODEL  LENGTH  HEIGHT  DEPTH  WALL CUTOUT  
 18,000 - 24,000 BTU  34 7/8"  70 1/2"  31"  49"H x 30"W  
 31,000 - 36,000 BTU  39 7/8"  70 1/2"  31"  49"H x 37"W  
 43,000 - 57,500 BTU  43 7/8"  84 7/8"  36"  58"H x 40"W  
 67,000 - 69,500 BTU  43 7/8"  94 7/8"  36"  58"H x 40"W  
           


 