explosion proof air conditioners

MATTICKS INDUSTRIES, INC.

explosion proof air conditioners

X-GUARDTM

CR29 Series

CABINET MOUNTED AIR CONDITIONING

FOR DIVISION 1 HAZARDOUS LOCATIONS

CLASS I, GROUPS BCD EXTERIOR TO THE ENCLOSURE

GENERAL PURPOSE INTERIOR

 


Unique single blower design allows for a general purpose motor to be used.

Access cover hinges open for easy access to all componets.

Quick and easy mounting of the unit to your cabinet.

Closed loop cooling system.

CFC-Free Refrigerant.

Thermostat controled

EMI/RFI noise suppressor.

 

2000 BTU COOLING @ 115 and 230 Volts 60Hz

4000 BTU Cooling @ 115 and 230 Volts 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

X-GUARD CR29 Series 2000 to 4000 BTU Cooling @ 60Hz

115/230 Volt

 MODEL  VOLTAGE  BTU/Hr @ 131degF  AMPS  BTU/Hr @ 95degF  AMPS  MAX. AIR TEMP F deg
 XGP-CR29-0216-G002-1BCD  115/1/60  2200  7.4  2000  6.0  131
 XGP-CR29-0226-G002-1BCD  230/1/60  2700  3.9  2300  3.3  131
 XGP-CR29-0416-G002-1BCD  115/1/60  4000  13.5  2800  9.6  131
 XGP-CR29-0426-G002-1BCD  230/1/60  4000  6.6  2800  5.3  131
             

X-GUARD CR29 Series 2000 to 4000 BTU Cooling @ 60Hz

with Optional Stainless Steel Housing

115/230 Volt

 MODEL  VOLTAGE  BTU/Hr @ 131degF  AMPS  BTU/Hr @ 95degF  AMPS  MAX. AIR TEMP F deg
 XGP-CR29-0216-G099-1BCD  115/1/60  2200  7.4  2000  6.0  131
 XGP-CR29-0226-G033-1BCD  230/1/60  2700  3.9  2300  3.3  131
 XGP-CR29-0416-G016-1BCD  115/1/60  4000  13.5  2800  9.6  131
 XGP-CR29-0426-G038-1BCD  230/1/60  4000  6.6  2800  5.3  131
             

 


X-GUARD CR29 Series 2000 to 4000 BTU Cooling @ 60Hz

with Optional Stainless Steel Housing and NEMA 4X

115/230 Volt

***NOTE: The units listed below are not Listed by ETL, they are In-House Listed

 MODEL  VOLTAGE  BTU/Hr @ 131degF  AMPS  BTU/Hr @ 95degF  AMPS  MAX. AIR TEMP F deg
 XGP-CR29-0216-G098-1BCD  115/1/60  2200  7.4  2000  6.0  131
 XGP-CR29-0226-G037-1BCD  230/1/60  2700  3.9  2300  3.3  131
 XGP-CR29-0416-G066-1BCD  115/1/60  4000  13.5  2800  9.6  131
 XGP-CR29-0426-G063-1BCD  230/1/60  4000  6.6  2800  5.3  131
             


 INSTALLATION INFORMATION  Over-All Height  Over-All Width  Over-All Depth    
 Unit Dimensions  29.5"  20.5"  8.75"    
 Return Air Opening (Top)  5.66"  11.44"      
 Supply Air Opening (Bottom)  3.56"  4"      
           


Matticks Industries, Inc. © 2013 | All Rights reserved

 

HOME PAGE